What Amp circuit breaker to use for 14G and for 12G telecommunication? What Amp circuit breaker should be used for 14G wire and...

What Amp circuit breaker should be used for 14G wire and which one for 12G flex?
When running new lines for lights we are using 14G telecommunication and for outlets we are using 12G wire. What are the guidelines for the circuit breaker Amp to game the wire quantify?

What if one uses 20 Amp circuit breaker for a 14G wire?
Answers:    #14 uses a MAXIMUM of 15A breaker, and #12 uses a MAXIMUM of 20A. There is no problem next to using bigger wire on a smaller breaker. In some cases, such as the distance the circuit runs from the panel, code requires that you use the subsequent biggest size of wire. Hope this help.
!4 ga is only permitted on a 15 amp breaker for lights or a single receptacle. 12 ga is a 20 amp breaker for common purposes. For certain other permitted use such as motors on faithful circuits, the rating may be different.